Fire Safety Assessment Checklist for the Manufacturing Facility & Factory
General Information
|
|
Sl. No.
|
Code Provision
|
1
|
Draft Report Date
|
2
|
Final Report Date
|
3
|
Are all Action Items From
Previous Assessment Completed?
|
4
|
Buildings in Complex
|
5
|
Is the building(s) owned
or rented by the Factory
|
6
|
Number of Building Levels
(Stories)
|
7
|
Approximate Building Area
(SF)
|
8
|
Date of Building
Construction
|
9
|
Date of Last Building
Renovation/Addition
|
10
|
Ancillary Structures in
Complex
|
11
|
Approximate Ancillary
Structures Area (SF)
|
12
|
Number of Occupants
|
13
|
Number of Ancillary
Levels (Stories)
|
Fire Protection
Construction
|
|
Sl. No.
|
Code Provision
|
14
|
Certificates of Occupancy
for each building have been issued and are on file.
|
15
|
Occupancy Type
|
16
|
Construction Type
|
17
|
Height of Highest
Occupied Floor Level Above Grade
|
18
|
Is the fire resistance
materials of structural members in good condition and free of damage?
|
19
|
Are openings and
penetrations through rated walls and/or assemblies protected?
|
20
|
Is each floor separated
with a fire-resistive rated construction barrier?
|
21
|
Are separations between
hazards provided with fire-resistive rated construction barriers.
|
22
|
Are exit enclosures
provided with fire-resistive rated construction barriers?
|
23
|
Are shafts provided with
the minimum fire-resistance rating?
|
24
|
Fire dampers installed on
air-conditioning and ventilation ducts appear to be in good condition and
operational.
|
25
|
If the building contains
a vertical opening known as an atrium, have provisions been made to comply
with Alliance Standard 3.7?
|
Fire Protection Systems
|
|
Sl. No.
|
Code Provision
|
26
|
Is the building protected
by an automatic sprinkler system?
|
27
|
Design criteria of
sprinkler system?
|
28
|
Commodity Class used for
the design of the sprinkler system?
|
29
|
Occupancy Classification
used for the design of the sprinkler system?
|
30
|
Are inspection,
maintenance, and testing procedures of the sprinkler system documented and up
to date?
|
31
|
Are identification signs
for the sprinkler system installed at the required locations?
|
32
|
Sprinkler system piping
is free of mechanical damage, leakage, and corrosion.
|
33
|
Sprinkler system piping
is not subjected to external loads by materials either resting on the pipe or
hung from the pipe?
|
34
|
Are hangers, bracing, and
restraints properly installed and supporting the system piping?
|
35
|
Sprinklers do not show
signs of leakage, are free of corrosion, have not been painted, and are not
physically damaged.
|
36
|
All valves controlling
the automatic sprinkler systems are<br />electrically supervised by a
listed fire alarm system control unit.
|
37
|
Does the automatic
sprinkler system have an approved audible device activated by waterflow equal
to the flow of one sprinkler?
|
38
|
Are sprinklers spaced and
installed at the required heights in order to provided required coverage and
protection?
|
39
|
Are storage racks and
shelves compliant based on class of commodity storage?<br />
|
40
|
Aisles in storage areas
are free of storage based on design criteria used for the sprinkler
system.<br />
|
41
|
All storage is maintained
with a 460 mm (18 in.) minimum clearance from the top of storage to the
sprinkler deflector.
|
42
|
Does the building have a
Standpipe System?
|
43
|
Are inspection,
maintenance, and testing procedures of the standpipe and hose system
documented and up to date? Including inspection and testing of hoses if
provided.
|
44
|
Is signage for the
standpipe system installed at required locations and on required components?
|
45
|
Standpipe system piping
is free of mechanical damage, leakage, and corrosion?
|
46
|
Are fire department
connections provided and clearly identified for the Fire Protection Systems?
|
47
|
Does the building have a
fire pump?
|
48
|
Are inspection,
maintenance, and testing procedures of the fire pump documented and up to
date?
|
49
|
Are portable fire
extinguishers installed throughout the building at required locations and
mounted at the correct height?
|
50
|
Portable fire
extinguishers have been selected based on potential fire class and hazards?
|
51
|
Fire extinguishers are
inspected, tested, and maintained as required.
|
52
|
Are there any other fire
suppression systems installed within the building?
|
53
|
Is the fire alarm and
detection system monitored by a central station monitoring service or
directly connected to the Fire Service and Civil Defense?
|
54
|
Trouble or alarm
notifications were not indicated on the fire alarm control panel.<br />
|
55
|
Are notification and
initiation devices for the fire alarm system installed at required locations
based on occupancy type?
|
Means of Egress
|
|
Sl. No.
|
Code Provision
|
56
|
Occupant loads on each
level (floor) do not exceed the capacity of the available means of egress.
|
57
|
Occupied roofs are
provided with the minimum number of exits required as a story.<br />
|
58
|
All occupied roofs are
provided with parapets or guards with a minimum height of 1067 mm<br
/>(42 in.).<br />
|
59
|
Occupant loads are posted
for every assembly and production floor in a conspicuous space near the main
point of egress.<br />
|
60
|
Aisles are provided with
the minimum unobstructed clear width of 0.9 m (36 in) based on occupant
loads.<br />
|
61
|
The path of egress along
the means of egress is not reduced at any point along the path of travel and
is sufficient for the occupant load.<br />
|
62
|
Means of egress have a
minimum ceiling height of 2.3 m (7 ft 6 in.) with projections from the
ceiling not less than 2.03 m (6 ft 8 in.).
|
63
|
Exit discharge is
directly to the exterior of the building, unless the requirements of 6.17.2
are met, at grade or provides direct access to grade. Exit discharge shall
not reenter a building.
|
64
|
Travel distance to reach
an exit does not exceed the maximum distance allowed by Occupancy Type.<br
/>
|
65
|
Exit access corridors
serving an occupant load exceeding 30 are separated by walls having a
fire-resistance rating of 1 hr.
|
66
|
Interior finishes for
means of egress meet the rating requirements for Class A, B and C materials.
|
67
|
Exits are limited to
Class A and Class B interior materials.
|
68
|
The number of means of
egress from any floor or story is not less than 2 except where a single exit is
permitted or where a greater number is required.<br />
|
69
|
The number of means of
egress from any floor or story is not less than 3 when the occupant load
exceeds 500 per story and not less than 4 when the occupant load exceeds 1000
per story.<br />
|
70
|
All paths of egress are
provided with compliant means of illumination.<br />
|
71
|
Means of egress are free
from impediments, obstructions, and stored materials.
|
72
|
Emergency power for means
of egress illumination is verified at least once per year. If battery
operated lights are used, these lights are tested on a monthly basis.
Functional testing of battery powered lights is provided for a minimum 90 min
once per year.
|
73
|
Doors are not locked in
the direction of egress under any conditions. All hasps, locks, slide bolts,
and other locking devices have been removed where required.<br />
|
74
|
Doors along the path of
egress have a minimum width of 0.8 m (32 in) and have required ratings.<br
/>
|
75
|
All doors in a means of
egress are of the side-hinged swinging type.<br />
|
76
|
Illuminated exit signs
are placed at entrances to exits and along the path of egress anywhere the
continuation of egress is not obvious or there is a change in the direction
of the path of travel.<br />
|
77
|
Changes in elevation of
walking surfaces do not exceed 6.35 mm (1/4 in) unless provided with a
beveled slope of 1 in 2 that does not exceed 12.7 mm (1/2 in).<br />
|
78
|
Illuminated exit signs
are provided with battery backup or emergency power and are continuously
illuminated.<br />
|
79
|
Emergency power for exit
signs is tested at least once per year. If battery operated, these lights are
tested on a monthly basis. Functional testing of battery powered signs is
provided for a minimum 90 min once per year.<br />
|
80
|
Exit signs have appropriate
illumination levels and contrasting graphics.<br />
|
81
|
Walking surfaces along
the path of egress are uniformly slip resistant.<br />
|
82
|
Compliant guards are
provided on the open sides of egress components where the elevation exceeds
760 mm (30 in) above the ground or floor below.
|
83
|
Stairs are constructed of
noncombustible materials.<br />
|
84
|
Stairs have a minimum
width of 0.9 m (35 in.).<br /><br />
|
85
|
Stair treads are of
nominal uniformity.<br />
|
86
|
Landings are provided on
both sides of doors used along the path of egress. Doors do not swing out
over stairs.<br />
|
87
|
Landings are provided
with the same width in the direction of egress travel as the stair clear
width provided at each level and at intermediate landings. Existing landings
that are less than the stair width, shall reduce the overall available
capacity of the stair.
|
88
|
Handrails are provided on
both sides of each stairway. Intermediate handrails are provided when the
stair width exceeds 2.2 m (87 in.). Handrails are not mounted lower than 760
mm (30 in.) or higher than 1100 mm (44 in.).<br />
|
89
|
Every door in a stair
enclosure serving more than 4 stories is provided with re-entry unless it
meets the requirements of Alliance Standards Part 6 Section 6.8.3.1.<br
/>
|
90
|
Exterior exit stairs are
separated from the building with the required rating. The rating of the
exterior wall shall extend 3.05 m (10 ft) beyond the ends of the stair
structure.
|
91
|
Interior exit stairways
and ramps terminate at an exit discharge except where terminating at a rated
exit passageway.
|
92
|
Stair designation signs
are provided at each floor entrance from the stair to the floor in English
and Bengali. Signs indicate the name of the stair and the floor level. Signs
are posted adjacent to the door.
|
93
|
Stairwells are not
utilized as storage spaces.<br />
|
94
|
Ramps used in a means of
egress do not reduce the overall means of egress width. The<br
/>minimum width shall be 1.1 m (44 in.).
|
95
|
Ramps do not have a
running slope greater than 1 in 8 (12.5 percent) and have handrails on both
sides of the ramp.<br />
|
Fire Safety Programs
|
|
Sl. No.
|
Code Provision
|
96
|
A Fire Safety Director
position has been filled.<br />
|
97
|
An emergency evacuation
plan has been developed and communicated to all employees.<br />
|
98
|
Emergency egress maps are
posted at the entrance to each exit stair or main point of egress.<br
/>
|
99
|
Fire Department
pre-planning has been completed.<br />
|
100
|
Fire Drills are conducted
at required intervals based on building use type.<br />
|
101
|
Are the required number
of people trained and certified in fire fighting, first aid, and rescue
training by the appropriate authority.<br />
|
102
|
A written housekeeping
policy is established and enforced.<br />
|
103
|
A hot-work permit program
has been established.<br />
|
104
|
Chemicals and other
flammable materials are stored within approved enclosures.<br />
|
105
|
Storage areas underneath
the cutting tables are clear of combustibles.
|
106
|
Training programs are
implemented and documented in accordance with the Alliance Safety Training
Curriculum.<br />
|
107
|
Smoking is only allowed
at designated areas.<br />
|
108
|
Are all applicable
permits up to date including Fire License & Boiler License.<br />
|
109
|
Are there additional
areas of non-compliance to report?
|
No comments:
Post a Comment