know that diesel engine is effective for peak load power plant. A diesel engine
can go to full load within 5 minutes but a steam plant unit might need over 12
hours to go to loading. With this advantage diesel engine has its own
limitation that it is very uncertain and not reliable. There is always prone to
some problems or difficulties. You can stop a good running engine and then
might fail to restart it – some problem is likely to occur.
So
care should be taken to start, stop, run, loading, unloading & specially
preserving preserve a diesel engine.
Start and stop procedure of diesel engine with different
fuels
The
diesel engine can be started and stopped on HFO (heavy fuel oil – furnace oil)
and Crude Oil. The preheating systems for the engine and the fuel feed system
should always be switched on, also during engine stop.
However,
if the engine for some reason is started and stopped on diesel oil (LFO), the
engines should be operated at high load and on diesel oil for at least 30
minutes before they are stopped. This will secure that there is only diesel oil
in the system.
Diesel Engine low load running and idling time
DIESEL
and HFO Engine might run in low load or without load (idle), but there is some
restriction to this type of running operation. Things should do according to
the engine manufacturers’ instruction.
As
example - for Wartsila 20 V32 Engine running idle.
If the
engine has been idling for more than 5 minutes, high load running (minimum 70%)
must be followed for minimum 60 minutes to clean up the engine.
· 1. Recommended idling time:
3–5 minute.
· 2. Maximum idling time: 30
minute.
Maintenance and calibration of engine safety automation
system
The
speed fluctuations in diesel engine is dangerous as per mechanical perspective.
Only 15% to 19% high to nominal speed is allowed. Say a 75o RPM engine has
safety shut down on 840 RPM and auto shut down on 880 RPM. In case of cooling
system – jacket water-cooling of diesel engine is important. The normal jacket
water cooling temperature is 85°C to 100°C, and for 110°C, there will be direct
shut down of engine. Also lower cooling water temperature will led in to normal
shut down.
There
are three automatic control modules in wartsila w20 v32 engine. They are namely
ESM – Engine safety module, Dedicated to fundamental safety of engine like over
speed, lube oil low pressure etc. MCM – Main control module, speed controller
of engine and controls start stop of engine. PDM – Power distribution module,
Supply power to ESM, MCM and other sensors includes in automation system.