Rated frequency of circuit breaker
Two
frequencies are currently used throughout the world: 50 Hz in Europe and 60 Hz
in America, a few countries use both frequencies. The rated frequency is either
50 Hz or 60 Hz.
The
performance of a circuit breaker is same for both the frequencies 50HZ and 60HZ
ac network. Same thermal effect and other performance for up to 60HZ of a
circuit breaker. Special consideration is required for frequency above 60HZ.
Switching sequence & Operating sequence of circuit
breaker
We
should not switch on or off a circuit breaker or operate a circuit arbitrarily;
there is some specific standard for switching and operating sequence of a
circuit breaker.
Switching sequence
Rated
switching sequence of circuit breaker according to IEC(International Electro
technical Commission), O – t – CO – t’ – CO. (cf: opposite diagram)
O :
represents opening operation
CO :
represents closing operation followed immediately by an opening operation
t =
time
So
after opening the circuit breaker there should be some time gap, then closing
operation. The the next time gap should be a little more. This is explained
below.
Operating sequence
Three
rated operating sequences exist:
v
slow: 0 – 3 minute – CO – 3 minute – CO
v
quick 1: O – 0.3 s – CO – 3 minute – CO
v
quick 2: O – 0.3 s – CO – 15 s – CO
Fig: Rated operating
sequence of circuit breaker