To
select the proper fuse or circuit breaker for Group Motor installations, you
must apply the specific rules of the National Electrical Code (NEC) for Group
Motor installations. This applies to a single circuit breaker or fuse for a
group of motors in the branch circuit that is single upstream short circuit
protection in a Group Motor installation.
Fig: Motor in the same branch circuit
Refer
to NEC (National Electric Code) section 430-53C and section 430-53D for proper
conductor ampacity selection. This applies to a single circuit breaker or fuse
for a group of motors in the branch circuit that is single upstream short
circuit protection in a Group Motor installation.
Calculating the circuit breaker size for group of motors
Example -1
Eight
motors with the sizes shown in Table are installed on a conveying system. Time-delay
fuses are used.
Motor Quantity
|
Rating (hp)
|
Voltage
|
Full-load ampere (FLA)
|
1
|
5
|
460
|
7.6
|
2
|
3
|
460
|
4.8
|
5
|
2
|
460
|
3.4
|
In
accordance with NEC section 430-52, section 430-53, and table 430-152, the
time-delay fuse must be sized as follows:
175%
FLA for largest motor + sum of FLAs for all other motors
⇒
(1.75 x 7.6) + (2 x 4.8) + (5 x 3.4) = 39.9 A
NEC
430-52 allows use of the next largest standard-size fuse—which in this case is
40 A. If nuisance tripping is a problem with this fuse selection, NEC does
allow 225% of the largest motor FLA to be used in lieu of 175% when calculating
the size. In this case, the calculation is as follows (the next largest
standard fuse size in this case is 45 A):
(2.25
x 7.6) + (2 x 4.8) + (5 x 3.4) = 43.7 A
Example -2
Motor Quantity
|
Rating (hp)
|
Voltage
|
FLA- Full load ampere
|
2
|
10
|
460
|
14
|
1
|
5
|
460
|
7.6
|
2
|
3
|
460
|
4.8
|
5
|
2
|
460
|
3.4
|
250%
FLA for largest motor + sum of FLAs for all other motors
⇒ (2.5
x 14) + 14 +7.6 + (2 x 4.8) + (5 x 3.4) = 83.2 A
If
nuisance tripping is a problem, the NEC allows for inverse-time circuit breaker
sizes that “shall in no case exceed 400% for full-load currents of 100 amps or
less, or 300% for full-load current greater than 100 amps.” In this case, the
calculation is as follows (the next largest standard inverse-time circuit
breaker size in this case is 110 A):
(4.0 x
14) + 14 +7.6 + (2 x 4.8) + (5 x 3.4) = 104.2 A
Fig: Motor
in branch circuit
No comments:
Post a Comment